Wednesday, September 17, 2014

Replacing a Furnace Blower Motor Control Board

It has gotten cold early this year, and I found myself firing up our furnace before the summer was officially over. I was thrilled to find that there was no hot air coming out of the vents.

Diagnosing a Bad Blower Motor or Blower Motor Control Board
I quickly realized that the blower motor was not coming on. For those not familiar with the different parts of a furnace, the blower motor is what forces the hot or cold air through the duct work and out of your vents.

The normal heating sequence of a gas furnace starting up goes something like this:

1. Thermostat calls for heat (24 volts AC is applied from the R terminal to the W terminal inside the thermostat)
2. Furnace inducer fan starts. The inducer fan creates a draft through the furnace, closing a pressure switch.
3. After the pressure switch is closed for a preset amount of time, the pilot light is lit by an electronic ignitor unit (older furnaces do not have this, and have a standing pilot instead).
4. A bimetal strip located near the pilot light heats up and closes a switch.
5. After this switch is closed for a preset amount of time, the main gas valve is permitted to open and the burners fire up.
6. After a preset amount of time, the blower motor will start and begin to blow the hot air through the ducts.

Step #6 was not happening for me, and the furnace would eventually shut down due to overheating.

In order to verify that the problem was not with the motor itself, I turned the FAN setting on the thermostat to "ON" from "AUTO". This tells the control board to turn on the fan regardless of whether heating or cooling is being called for by the thermostat. The blower motor started up when I did this, so I knew the problem was likely with the control board.

Locating the Control Board

The control board should be located near the blower motor, and is likely concealed by a steel electrical junction box with warning labels on it. If you're not sure where the blower motor is, it should be right next to the air filter. If you don't know where the air filter is....well then you need to find it, and change your air filter! Notice in the image below that there is a spring load switch in the upper left hand side of this compartment. This switch cuts the power to this compartment when the cover is off for safety purposes.

Furnace Blower Motor Compartment
After taking off the cover of the steel electrical box, you should see the blower motor control board (see image below). 

 Control Power Transformer & Blower Motor Control Board
The large objects in the middle are relays, which send power to the blower motor when the command to turn on the motor is received. These are old style relays, and they have a translucent cover on them that allows you to actually see a spark when they open and close the circuit. The relay on the left is for the "LOW" blower motor speed, used for the heating mode. The relay on the right is for the "HIGH" blower motor speed, used for the cooling mode, as well as for when the switch on the thermostat is set to "ON".

The relay on the left was not sending power to the fan when it received the command to do so. After removing the relay, it was no mystery why. See below.

Burned up relay
It should be noted that these particular relays are not intended to be easily replaceable; I actually pried this relay out of its solder joints. Also, it's not cost effective or logical to try to replace this antiquated relay. Depending on the type of control board the furnace uses, there is likely an updated version of the board that can be purchased for a reasonable price.

Removing the Control Board

The board was held on with (2) 1/4" hex screws near the bottom. In fact, it seems like every fastener on my furnace is 1/4" hex. I'm guessing this is the industry standard. I made sure to take note of where the existing wires were terminated.

Thermostat, humidifier, and A/C control wire terminations

There is also a plug connector where the board sends and receives control signals to the other components. This pries out easily.

Plug connector pries out

Plug connector removed

Installing a Replacement Control Board

I was able to find a brand new replacement board made by ICM on eBay for $45. The replacement board has some additional features, a fuse for protection against short circuits, and modern electronic components.

Old board on the left, new on the right

Looking at the back of the circuit board, notice that there are circuit board traces going through one of the screw holes. It is important to make sure the board is screwed in at this point, as it is grounding the board to the furnace enclosure.

Control board grounding point

There are many wires that need to be terminated on the new board. The thicker wires will have spade connectors on them, which allow them to be easily plugged into the terminals on the board. The board will also have a few letters next to each connector to indicate what should be plugged in where. See below for the 120V connections on the new board.

New control board 120V connections
Here's a summary of what the identifiers on the board mean:

LO: This is the red wire that goes to the blower motor. This terminal is energized when the low speed of the blower motor is called for by the heating cycle.

HI: This is the black wire that goes to the blower motor. This terminal is energized when the high speed of the blower motor is called for by the cooling cycle, or by the fan "ON" switch on the thermostat.

PR1: This stands for primary #1, referring to the primary side of the control power transformer. The black wire from the transformer gets terminated here.

L1: This stands for line #1, and gets connected to the incoming hot wire of the 120V circuit, which is the black wire

PR2: Primary #2. The white wire from the transformer gets terminated here.

L2: Line #2. The neutral wire (white) of the incoming 120V gets terminated here.

COM: Common. The white wire from the blower motor gets terminated here.

SEC1 & SEC2 (not pictured): Secondary #1 & #2. This is the 24V which power the control circuits. The red and blue wires, respectively, get terminated here.

The thermostat wires also need to be terminated to the new board. Here's the industry standard color code:

White -----> W    Heat
Yellow -----> Y   A/C
Green ------> G  Fan
Black -----> C   Common
Red -----> R  +24V

Go here for a much more in depth discussion of standard colors and terminal designations.

End Result
Success! The new control board works as expected, and we saved a few hundred dollars by not calling out a tech.



DISCLAIMER: I am not a certified HVAC technician. This information is not representative of all furnaces, nor is there any guarantee of the accuracy of this information. Wire colors, while usually following the industry standards, can be different. If you are not comfortable with basic wiring concepts or the basic operation of a furnace, call a certified HVAC technician. ALWAYS turn off the furnace power circuit before working on it.


Sunday, January 5, 2014

Creating a Data Closet


Over time I've accumulated a lot of different pieces of equipment to run the various systems in my home. It didn't take me long to realize that I needed a dedicated space to place and organize all of this stuff. Here's a list of all my equipment:

HTPC (Home Theater PC)
Next Generation Remote Control Extender
Silicondust HDHomeRun Prime network tuner
Ceton Echo Windows Media Center Extender
Sewell 1x4 HDMI splitter
Motorola tuning adapter
Zoom 5341J DOCSIS 3.0 cable modem
12-port Cat 6 patch panel
Asus 8-port gigabit switch
Asus 5-port gigabit switch
PCT 4-port cable/internet signal amplifier
Various coax splitters
ISY994i home automation controller
Power Strip

One way to deal with all of this equipment is to purchase an equipment rack. I briefly considered going this route until I added up the cost of purchasing a rack and the necessary accessories. Another option is to install a structured wiring panel. These are great for keeping everything neat and organized, but this type of installation seems to have a lot of unnecessary costs like special shelves and power receptacles that will fit in the panel.

In the end, I decided most cost effective and functional installation for me was to just fasten some OSB (Oriented Strand Board, a cheap alternative to plywood) to the wall in an underutilized storage room underneath the stairs. This worked out great because the storage room is in a central location in my house.

Various Equipment Mounted to OSB

IR Extender and HTPC mounted off the floor in case of basement flooding

I'll admit it isn't pretty, but it has worked very well for me. It's extremely simple to swap out equipment, and there's plenty of room to work. Also, there's no special equipment needed to mount the components. Many components come with holes in the back for attaching to screws fastened in the wall. For components that don't have holes in the back, I just use zip ties with screw holes.

All of the wiring serving the coax and Cat 6 jacks in my house run back to this central location. This gives me a lot of flexibility. For example, I'm able to locate my wireless router in a room on the first floor rather than in the basement in order to have a stronger wireless signal on the first floor. This may not always be feasible though; if you have a finished basement with drywall ceilings, running new wiring can be difficult and frustrating.

So, if you're looking for a way to organize all of your AV, cable, and networking equipment, here's the process:

1. Identify a Location - Ideally your data closet should be centrally located, but it doesn't have to be. Verify that it is feasible to route existing and new wiring to this location.
2. Relocate or extend any existing wiring - My coax line from the cable company was split in the basement ceiling, and then went off to my cable modem and TV locations on the first floor. You'll likely need to do something similar if your data closet is in a different location than where the coax enters the house. Also, ideally you want all of the cable and network jacks in the house to terminate in this closet.
3. Layout the components - Locate the components in a logical manor, and try to keep some separation between different systems. This isn't critical, but it will help keep things organized and will reduce the number of cables that have to cross over each other.
4. Power - You'll need a lot of receptacles to plug in your components. Consider running a dedicated circuit to the closet and installing a power strip with a lot of receptacles. The one you see in the photo above can be purchased from Harbor Freight for around $20.
5. Fasten the components to the wall and make all final connections

Updating Thermostat Wiring

When I started researching replacement thermostats that will interface with my home automation system, I noticed that most of these thermostats require 24 volts to operate in lieu of the battery operated model that is currently installed. The 24 volts is normally provided by the 120VAC to 24VAC furnace transformer.

The reason that this was a problem for me is that I only had 4 wires coming to my thermostat; a 5th wire is needed in order to provide 24VAC to the thermostat. There are workarounds to this problem, such as this "add-a-wire" adapter. However, my house is a ranch with a full basement, and I was confident that I could easily run new wiring.

While I could have purchased 18/5 (a cable with 5 #18 AWG wires), it made more sense to run additional wires for use in the future, since many modern high efficiency HVAC systems are two-stage. I ended up purchasing 18/8 wire, which is 64 cents/foot at Lowes as of January 2014. I only needed 45 feet, so this worked out to cost less than purchasing a a 4 to 5 wire adapter, and I don't have another electrical component in the system that could fail in the future.

18/8 thermostat wire
If you are running into this same situation, and have a basic understanding of your furnace and AC control wiring, I would recommend putting in 18/8 in order to future-proof your system. That being said, if you have no way to fish new wires to your thermostat locations, the add-a-wire adapter is probably your best bet.